MEPS Requirements for Ballasts for Linear Fluorescent Lamps

From 1 March 2003, ballasts for linear fluoescent lamps manufactured in or imported into Australia must comply with Minimum Energy Performance (MEPS) requirements which are set out in AS/NZS 4783.2-2002.

MEPS DOES apply to the following types of ballasts:

Ballasts within the scope of MEPS must also be marked with their energy efficiency by way of their Energy Efficiency Index (EEI), the details of which are also specified in AS/NZS 4783.2-2002. AS/NZS 4783.2-2002 also requires that ballasts within the scope of MEPS be designed to comply with the relevant performance requirements of IEC60921 for ferromagnetic ballasts and IEC60929 for electronic ballasts. These standards are also published by Standards Australia as AS/NZS60921 and AS/NZS60929.

MEPS DOES NOT apply to the following types of ballasts:

The Minimum Energy Performance Standards (MEPS) requirements are set out as maximum allowable total circuit power when tested in accordance with AS/NZS 4783.1. These are set out in the tables below when tested to AS/NZS4783.1 (see details on ballast test methods):

Maximum allowable total circuit power is shown in Tables 1-3 of AS/NZS 4783.2 below. A copy of the standard can be purchased from SAI Global under licence from Standards Australia.

TABLE 1
BALLASTS FOR FLUORESCENT LAMPS - EEI CLASSIFICATION FOR RATED VOLTAGE >250 V

 
Lamp type
and arrangement
Nominal
lamp
power*
Watts
 
 
ILCOS code
 
Maximum corrected total input power, Watts
Energy Efficiency Index (EEI) classification
A1# A2 A3 B1 B2 C D
Linear


15 FD-15-E-G13-26/450 <18.0 <16.0 <18.0 <21.0 <24.0 <25.0 >25.0
18 FD-18-E-G13-26/600 <21.0 <19.0 <21.0 <24.0 <27.0 <28.0 >28.0
30 FD-30-E-G13-26/895 <33.0 <31.0 <33.0 <36.0 <39.0 <40.0 >40.0
36 FD-36-E-G13-26/1200 <38.0 <36.0 <38.0 <41.0 <44.0 <45.0 >45.0
38 FD-38-E-G13-26/1047 <40.0 <38.0 <40.0 <43.0 <46.0 <47.0 >47.0
58 FD-58-E-G13-26/1500 <59.0 <55.0 <59.0 <64.0 <68.0 <70.0 >70.0
70 FD-70-E-G13-26/1800 <72.0 <68.0 <72.0 <77.0 <81.0 <83.0 >83.0
NOTES:
1. Refer to AS/NZS 61231, International lamp coding system (ILCOS)
2. Applies only to mains frequency ferromagnetic ballasts with two-wire connection and with an external starter.

* Nominal values shown may have different rating values. Refer to the relevant lamp data sheet.
# Refer Clause 5.3.2

TABLE 2
BALLASTS FOR FLUORESCENT LAMPS - EEI CLASSIFICATION FOR RATED VOLTAGE >240 V AND < 250V

 
Lamp type
and arrangement
Nominal
lamp
power*
Watts
 
 
ILCOS code
 
Maximum corrected total input power, Watts
Energy Efficiency Index (EEI) classification
A1# A2 A3 B1 B2 C D
Linear


15 FD-15-E-G13-26/450 <18.0 <16.0 <18.0 <21.0 <23.5 <25.0 >25.0
18 FD-18-E-G13-26/600 <21.0 <19.0 <21.0 <24.0 <26.5 <28.0 >28.0
30 FD-30-E-G13-26/895 <33.0 <31.0 <33.0 <36.0 <38.5 <40.0 >40.0
36 FD-36-E-G13-26/1200 <38.0 <36.0 <38.0 <41.0 <43.5 <45.0 >45.0
38 FD-38-E-G13-26/1047 <40.0 <38.0 <40.0 <43.0 <45.5 <47.0 >47.0
58 FD-58-E-G13-26/1500 <59.0 <55.0 <59.0 <64.0 <67.5 <70.0 >70.0
70 FD-70-E-G13-26/1800 <72.0 <68.0 <72.0 <77.0 <80.5 <83.0 >83.0
NOTES:
1. Refer to AS/NZS 61231, International lamp coding system (ILCOS)
2. Applies only to mains frequency ferromagnetic ballasts with two-wire connection and with an external starter.

* Nominal values shown may have different rating values. Refer to the relevant lamp data sheet.
# Refer Clause 5.3.2

TABLE 3
BALLASTS FOR FLUORESCENT LAMPS - EEI CLASSIFICATION

 
Lamp type
and arrangement
Nominal
lamp
power*
Watts
 
 
ILCOS code
 
Maximum corrected total input power, Watts
Energy Efficiency Index (EEI) classification
A1# A2 A3 B1 B2 C D
Linear


15 FD-15-E-G13-26/450 <18.0 <16.0 <18.0 <21.0 <23.5 <25.0 >25.0
18 FD-18-E-G13-26/600 <21.0 <19.0 <21.0 <24.0 <26.0 <28.0 >28.0
30 FD-30-E-G13-26/895 <33.0 <31.0 <33.0 <36.0 <38.0 <40.0 >40.0
36 FD-36-E-G13-26/1200 <38.0 <36.0 <38.0 <41.0 <43.0 <45.0 >45.0
38 FD-38-E-G13-26/1047 <40.0 <38.0 <40.0 <43.0 <45.0 <47.0 >47.0
58 FD-58-E-G13-26/1500 <59.0 <55.0 <59.0 <64.0 <67.0 <70.0 >70.0
70 FD-70-E-G13-26/1800 <72.0 <68.0 <72.0 <77.0 <80.0 <83.0 >83.0
Compact 2 tube


18 FSD-18-E-2G11 <21.0 <19.0 <21.0 <24.0 <26.0 <28.0 >28.0
24 FSD-24-E-2G11 <27.0 <25.0 <27.0 <30.0 <32.0 <34.0 >34.0
36 FSD-36-E-2G11 <38.0 <36.0 <38.0 <41.0 <43.0 <45.0 >45.0
40 FSDH-40-L/P-2G11 <46.0 <44.0 <46.0 - - - -
55 FSDH-55-L/P-2G11 <63.0 <59.0 <63.0 - - - -
Compact 4 tube flat



 
18 FSS-18-E-2G10 <21.0 <19.0 <21.0 <24.0 <26.0 <28.0 >28.0
24 FSS-24-E-2G10 <27.0 <25.0 <27.0 <30.0 <32.0 <34.0 >34.0
36 FSS-36-E-2G10 <38.0 <36.0 <38.0 <41.0 <43.0 <45.0 >45.0
Compact 4 tube (not flat)


10 FSQ-10-E-G24q = 1
FSQ-10-I-G24d = 1
<13.0 <11.0 <13.0 <14.0 <16.0 <18.0 >18.0
13 FSQ-13-E-G24q = 1
FSQ-13-I-G24d = 1
<16.0 <14.0 <16.0 <17.0 <19.0 <21.0 >21.0
18 FSQ-18-E-G24q = 2
FSQ-18-I-G24d = 2
<21.0 <19.0 <21.0 <24.0 <26.0 <28.0 >28.0
26 FSQ-26-E-G24q = 3
FSQ-26-I-G24d = 3
<29.0 <27.0 <29.0 <32.0 <34.0 <36.0 >36.0
Compact 6 tube


18 FSM-18-I-GX24d = 2
FSM-18-E-G24q = 2
<21.0 <19.0 <21.0 <24.0 <26.0 <28.0 >28.0
26 FSM-26-I-GX24d = 3
FSM-13-E-G24q = 1
<29.0 <27.0 <29.0 <32.0 <34.0 <36.0 >36.0
32 FSSMH-32-L/P-GX24q=4 <39.0 <36.0 <39.0 - - - -
42 FSMH-42-L/P-GX24q = 4 <49.0 <46.0 <49.0 - - - -
Compact 2D

(double D)


10 FSS-10-E-GR10q
FSS-10-L/P/H-GR10q
<13.0 <11.0 <13.0 <14.0 <16.0 <18.0 >18.0
26 FSS-16-I-GR8
FSS-16-E-GR10q
FSS-16-L/P/H-GR10q
<19.0 <17.0 <19.0 <21.0 <23.0 <25.0 >25.0
21 FSS-21-E-GR10q
FSS-21-L/P/H-GR10q
<24.0 <22.0 <24.0 <27.0 <29.0 <31.0 >31.0
28 FSS-28-I-GR8
FSS-28-E-GR10q
FSS-28-L/P/H-GR10q
<31.0 <29.0 <31.0 <34.0 <36.0 <38.0 >38.0
38 FSS-38-E-GR10q
FSS-38-L/P/H-GR10q
<40.0 <38.0 <40.0 <43.0 <45.0 <47.0 >47.0
55 FSS-55-E-GRY10q = 3
FSS-55-L/P/H-GRY10q = 3
<63.0 <59.0 <63.0 - - - -
NOTE: Refer to AS/NZS 61231, International lamp coding system (ILCOS)

* Nominal values shown may have different rating values. Refer to the relevant lamp data sheet.
# Refer Clause 5.3.2