Since 1 October 2001, three phase electric motors from 0.73kW to <185kW manufactured in or imported into Australia must comply with Minimum Energy Performance (MEPS) requirements which are set out in AS/NZS 1359.5-2000. MEPS does not apply to submersible motors, integral motor-gear systems, variable or multi-speed motors or those rated only for short duty cycles (IEC 60034-2 duty rating S2). Rewound motors are not required to comply with MEPS.
The Minimum Energy Performance Standards requirements are set out as minimum efficiency levels. These are set out in the tables below for Test Method B (AS 1359.102.1) and Test Method A (AS/NZS 1359.102.3) (see details on motor test methods).
From 1 April 2006, MEPS levels for three phase electric motors were revised to become more stringent. The "High Efficiency" level from 2001 became the MEPS level on 1 April 2006. From 1 April 2005 a revised "High Efficiency" level came into force. These new MEPS and high efficiency requirements are set out in detail in AS/NZS 1359.5-2004 which was published in September 2004. This standard supercedes AS/NZS 1359.5-2000.
MEPS levels and "High Efficiency" levels are set out in the tables as follows:
A copy of the standard can be purchased from SAI Global under licence from Standards Australia.
| Rated output kW |
Minimum efficiency % |
|||
|---|---|---|---|---|
| 2 pole | 4 pole | 6 pole | 8 pole | |
| 0.73 | 72.3 | 72.7 | 70.7 | 66.7 |
| 0.75 | 72.3 | 72.7 | 70.7 | 66.7 |
| 1.1 | 74.6 | 74.6 | 73.6 | 69.9 |
| 1.5 | 76.9 | 76.9 | 75.7 | 73.0 |
| 2.2 | 79.5 | 79.5 | 78.1 | 76.1 |
| 3 | 81.2 | 81.2 | 79.9 | 78.2 |
| 4 | 82.8 | 82.8 | 81.6 | 80.1 |
| 5.5 | 84.4 | 84.4 | 83.3 | 82.0 |
| 7.5 | 85.8 | 85.8 | 84.7 | 83.7 |
| 11 | 87.2 | 87.2 | 86.4 | 85.6 |
| 15 | 88.3 | 88.3 | 87.7 | 87.1 |
| 18.5 | 89.0 | 89.0 | 88.6 | 88.0 |
| 22 | 89.5 | 89.5 | 89.1 | 88.7 |
| 30 | 90.5 | 90.5 | 90.2 | 89.9 |
| 37 | 91.1 | 91.1 | 90.8 | 90.6 |
| 45 | 91.7 | 91.7 | 91.5 | 91.2 |
| 55 | 92.2 | 92.2 | 92.0 | 91.8 |
| 75 | 92.9 | 92.9 | 92.8 | 92.7 |
| 90 | 93.4 | 93.2 | 93.2 | 93.0 |
| 110 | 93.8 | 93.8 | 93.7 | 93.5 |
| 132 | 94.2 | 94.1 | 94.1 | 93.8 |
| 150 | 94.5 | 94.5 | 94.4 | 94.1 |
| <185 | 94.5 | 94.5 | 94.4 | 94.1 |
| NOTES: 1. For intermediate vales of rated output, the efficiency shall be determined by linear interpolation. 2. Tolerances specified in Table 1.1 of AS/NZS 1359.5 are applicable to the above values only in the case of a verification test. |
||||
| Rated output kW |
Minimum efficiency % |
|||
|---|---|---|---|---|
| 2 pole | 4 pole | 6 pole | 8 pole | |
| 0.73 | 78.8 | 80.5 | 76.0 | 71.8 |
| 0.75 | 78.8 | 80.5 | 76.0 | 71.8 |
| 1.1 | 80.6 | 82.2 | 78.3 | 74.7 |
| 1.5 | 82.6 | 83.5 | 79.9 | 76.8 |
| 2.2 | 84.0 | 84.9 | 81.9 | 79.4 |
| 3 | 85.3 | 86.0 | 83.5 | 81.3 |
| 4 | 86.3 | 87.0 | 84.7 | 82.8 |
| 5.5 | 87.2 | 87.9 | 86.1 | 84.5 |
| 7.5 | 88.3 | 88.9 | 87.3 | 86.0 |
| 11 | 89.5 | 89.9 | 88.7 | 87.7 |
| 15 | 90.3 | 90.8 | 89.6 | 88.9 |
| 18.5 | 90.8 | 91.2 | 90.3 | 89.7 |
| 22 | 91.2 | 91.6 | 90.8 | 90.2 |
| 30 | 92.0 | 92.3 | 91.6 | 91.2 |
| 37 | 92.5 | 92.8 | 92.2 | 91.8 |
| 45 | 92.9 | 93.1 | 92.7 | 92.4 |
| 55 | 93.2 | 93.5 | 93.1 | 92.9 |
| 75 | 93.9 | 94.0 | 93.7 | 93.7 |
| 90 | 94.2 | 94.4 | 94.2 | 94.1 |
| 110 | 94.5 | 94.7 | 94.5 | 94.5 |
| 132 | 94.8 | 94.9 | 94.8 | 94.8 |
| 150 | 95.0 | 95.2 | 95.1 | 95.2 |
| <185 | 95.0 | 95.2 | 95.1 | 95.2 |
| NOTES: 1. For intermediate vales of rated output, the efficiency shall be determined by linear interpolation. 2. Tolerances specified in Table 1.1 of AS/NZS 1359.5 are applicable to the above values only in the case of a verification test. |
||||
| Rated output kW |
Minimum efficiency % |
|||
|---|---|---|---|---|
| 2 pole | 4 pole | 6 pole | 8 pole | |
| 0.73 | 81.4 | 82.9 | 78.8 | 75.0 |
| 0.75 | 81.4 | 82.9 | 78.8 | 75.0 |
| 1.1 | 83.0 | 84.5 | 80.9 | 77.6 |
| 1.5 | 84.8 | 85.6 | 82.4 | 79.6 |
| 2.2 | 86.2 | 86.9 | 84.2 | 81.9 |
| 3 | 87.2 | 87.8 | 85.6 | 83.6 |
| 4 | 88.1 | 88.7 | 86.7 | 85.0 |
| 5.5 | 88.9 | 89.5 | 87.9 | 86.5 |
| 7.5 | 89.9 | 90.4 | 89.0 | 87.8 |
| 11 | 90.9 | 91.3 | 90.2 | 89.3 |
| 15 | 91.6 | 92.1 | 91.0 | 90.4 |
| 18.5 | 92.1 | 92.4 | 91.6 | 91.1 |
| 22 | 92.4 | 92.8 | 92.1 | 91.5 |
| 30 | 93.1 | 93.4 | 92.8 | 92.4 |
| 37 | 93.6 | 93.8 | 93.3 | 92.9 |
| 45 | 93.9 | 94.1 | 93.7 | 93.5 |
| 55 | 94.2 | 94.4 | 94.1 | 93.9 |
| 75 | 94.8 | 94.9 | 94.6 | 94.6 |
| 90 | 95.0 | 95.2 | 95.0 | 94.9 |
| 110 | 95.3 | 95.5 | 95.3 | 95.3 |
| 132 | 95.5 | 95.6 | 95.5 | 95.5 |
| 150 | 95.7 | 95.9 | 95.8 | 95.9 |
| <185 | 95.7 | 95.9 | 95.8 | 95.9 |
| NOTES: 1. For intermediate vales of rated output, the efficiency shall be determined by linear interpolation. 2. Tolerances specified in Table 1.1 of AS/NZS 1359.5 are applicable to the above values only in the case of a verification test. |
||||
| Rated output kW |
Minimum efficiency % |
|||
|---|---|---|---|---|
| 2 pole | 4 pole | 6 pole | 8 pole | |
| 0.73 | 74.0 | 74.4 | 72.4 | 68.4 |
| 0.75 | 74.0 | 74.4 | 72.4 | 68.4 |
| 1.1 | 76.2 | 76.2 | 75.2 | 71.5 |
| 1.5 | 78.5 | 78.5 | 77.3 | 74.6 |
| 2.2 | 81.0 | 81.0 | 79.6 | 77.6 |
| 3 | 82.6 | 82.6 | 81.4 | 79.7 |
| 4 | 84.2 | 84.2 | 83.0 | 81.5 |
| 5.5 | 85.7 | 85.7 | 84.6 | 83.3 |
| 7.5 | 87.0 | 87.0 | 86.0 | 85.0 |
| 11 | 88.4 | 88.4 | 87.6 | 86.8 |
| 15 | 89.4 | 89.4 | 88.8 | 88.2 |
| 18.5 | 90.0 | 90.0 | 89.6 | 89.0 |
| 22 | 90.5 | 90.5 | 90.1 | 89.7 |
| 30 | 91.4 | 91.4 | 91.1 | 90.8 |
| 37 | 92.0 | 92.0 | 91.7 | 91.5 |
| 45 | 92.5 | 92.5 | 92.3 | 92.0 |
| 55 | 93.0 | 93.0 | 92.8 | 92.6 |
| 75 | 93.6 | 93.6 | 93.5 | 93.4 |
| 90 | 94.1 | 93.9 | 93.9 | 93.7 |
| 110 | 94.4 | 94.4 | 94.3 | 94.1 |
| 132 | 94.8 | 94.7 | 94.7 | 94.4 |
| 150 | 95.0 | 95.0 | 94.9 | 94.7 |
| <185 | 95.0 | 95.0 | 94.9 | 94.7 |
| NOTES: 1. For intermediate vales of rated output, the efficiency shall be determined by linear interpolation. 2. Tolerances specified in Table 1.1 of AS/NZS 1359.5 are applicable to the above values only in the case of a verification test. |
||||
| Rated output kW |
Minimum efficiency % |
|||
|---|---|---|---|---|
| 2 pole | 4 pole | 6 pole | 8 pole | |
| 0.73 | 80.5 | 82.2 | 77.7 | 73.5 |
| 0.75 | 80.5 | 82.2 | 77.7 | 73.5 |
| 1.1 | 82.2 | 83.8 | 79.9 | 76.3 |
| 1.5 | 84.1 | 85.0 | 81.5 | 78.4 |
| 2.2 | 85.6 | 86.4 | 83.4 | 80.9 |
| 3 | 86.7 | 87.4 | 84.9 | 82.7 |
| 4 | 87.6 | 88.3 | 86.1 | 84.2 |
| 5.5 | 88.5 | 89.2 | 87.4 | 85.8 |
| 7.5 | 89.5 | 90.1 | 88.5 | 87.2 |
| 11 | 90.6 | 91.0 | 89.8 | 88.8 |
| 15 | 91.3 | 91.8 | 90.7 | 90.0 |
| 18.5 | 91.8 | 92.2 | 91.3 | 90.7 |
| 22 | 92.2 | 92.6 | 91.8 | 91.2 |
| 30 | 92.9 | 93.2 | 92.5 | 92.1 |
| 37 | 93.3 | 93.6 | 93.0 | 92.7 |
| 45 | 93.7 | 93.9 | 93.5 | 93.2 |
| 55 | 94.0 | 94.2 | 93.9 | 93.7 |
| 75 | 94.6 | 94.7 | 94.4 | 94.4 |
| 90 | 94.8 | 95.0 | 94.8 | 94.7 |
| 110 | 95.1 | 95.3 | 95.1 | 95.1 |
| 132 | 95.4 | 95.5 | 95.4 | 95.4 |
| 150 | 95.5 | 95.7 | 95.6 | 95.7 |
| <185 | 95.5 | 95.7 | 95.6 | 95.7 |
| NOTES: 1. For intermediate vales of rated output, the efficiency shall be determined by linear interpolation. 2. Tolerances specified in Table 1.1 of AS/NZS 1359.5 are applicable to the above values only in the case of a verification test. |
||||
| Rated output kW |
Minimum efficiency % |
|||
|---|---|---|---|---|
| 2 pole | 4 pole | 6 pole | 8 pole | |
| 0.73 | 82.9 | 84.5 | 80.4 | 76.5 |
| 0.75 | 82.9 | 84.5 | 80.4 | 76.5 |
| 1.1 | 84.5 | 85.9 | 82.4 | 79.1 |
| 1.5 | 86.2 | 87.0 | 83.8 | 81.0 |
| 2.2 | 87.5 | 88.2 | 85.5 | 83.3 |
| 3 | 88.5 | 89.1 | 86.9 | 84.9 |
| 4 | 89.3 | 89.9 | 87.9 | 86.2 |
| 5.5 | 90.1 | 90.7 | 89.1 | 87.7 |
| 7.5 | 90.9 | 91.5 | 90.1 | 88.9 |
| 11 | 91.9 | 92.2 | 91.2 | 90.3 |
| 15 | 92.5 | 92.9 | 92.0 | 91.4 |
| 18.5 | 92.9 | 93.3 | 92.5 | 92.0 |
| 22 | 93.3 | 93.6 | 92.9 | 92.4 |
| 30 | 93.9 | 94.2 | 93.6 | 93.2 |
| 37 | 94.2 | 94.5 | 94.0 | 93.7 |
| 45 | 94.6 | 94.8 | 94.4 | 94.2 |
| 55 | 94.9 | 95.0 | 94.8 | 94.6 |
| 75 | 95.4 | 95.5 | 95.2 | 95.2 |
| 90 | 95.5 | 95.7 | 95.5 | 95.5 |
| 110 | 95.8 | 96.0 | 95.8 | 95.8 |
| 132 | 96.1 | 96.1 | 96.1 | 96.1 |
| 150 | 96.1 | 96.3 | 96.2 | 96.3 |
| <185 | 96.1 | 96.3 | 96.2 | 96.3 |
| NOTES: 1. For intermediate vales of rated output, the efficiency shall be determined by linear interpolation. 2. Tolerances specified in Table 1.1 of AS/NZS 1359.5 are applicable to the above values only in the case of a verification test. |
||||