MEPS Requirements for Single Phase and Three Phase Air Conditioners to 65kW Cooling Capacity

Since 1 October 2001, three phase air conditioners with a cooling capacity of up to 65kW manufactured in or imported into Australia must comply with Minimum Energy Performance (MEPS) requirements. MEPS requirements are set out in AS/NZS 3823.2-2009. MEPS covers three phase non-ducted or ducted room air conditioners of the vapour compression type of up to 65kW cooling (commercial or residential) within the scope of AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3, as applicable.

Since 1 October 2004, all single phase air conditioners manufactured in or imported into Australia must comply with Minimum Energy Performance (MEPS) requirements. MEPS requirements are set out in AS/NZS 3823.2-2009. MEPS covers single phase non-ducted or ducted room air conditioners of the vapour compression type (commercial or residential) within the scope of AS/NZS 3823.1.1 or AS/NZS 3823.1.2 or AS/NZS 3823.1.3, as applicable.

AS/NZS 3823.1.1 and AS/NZS 3823.1.2 and AS/NZS 3823.1.3 cover equipment utilizing one or more refrigeration systems with one outdoor unit and one or more indoor units controlled by a single thermostat/controller. They cover equipment utilizing single, multiple and variable capacity components. Examples of equipment types covered include those with a single indoor control such as single packaged units, packaged ducted units, double and triple split systems and single split systems and water sourced heat pumps.

New MEPS and energy labelling requirements for air conditioners with a cooling output up to 65kW come into force on 1 April 2010 with transitional arrangements commencing in October 2009. There will be further changes in 2011. Details are set out in the Labelling and MEPS Transition Fact Sheet  (October 2009) and in AS/NZS3823.2-2009 which was published on 6 October 2009.

AS/NZS 3823.2-2009 requires the determination of Power Consumption in Non Operative Mode (Clause 2.4). The non-operating power of an air conditioner is the average power consumption of the air conditioner when not providing a cooling, heating or air circulation function for the user as determined in accordance with Appendix G. In accordance with Appendix G, where the determination of the Power Consumption in Non Operative Mode is affected by temperature and/or the operating schedule, information in relevant climate and operating schedule file shall be used to determine this power as specified. This linked Excel file provides a full temperature and operating profile for cooling mode and heating mode: Link to PDF Operating/temperature schedule for ACDB Climate 28 (Excel, 4.1 MB). Note that different profiles are used to separately assess heating mode and cooling mode.

Key Regulatory Dates

The following are key dates with respect to new requirements for air conditioners*:

*NOTE: October 2009: Link to PDF Stakeholder Letter and Link to PDF Keydates Table advising of recent energy rating label changes for Air Conditioners, Refrigerators and Freezers.

More stringent MEPS levels beyond 2011 are currently under consideration.

Products manufactured or imported must comply with the relevant requirements and MEPS levels at the time of manufacture or importation. Once registered to these requirements, products manufactured or imported prior to any new MEPS date can continue to be sold after new MEPS levels come into force. Details related to stock that has been imported into Australia or manufactured in Australia before 1st April 2010 are set out in the Administrative Guidelines (refer to MEPS transition arrangements, clause 3.2.2).

Test procedures for single and three phase units are the same: see requirements for air conditioners.

Exemptions: The following air conditioner types are exempted from the requirements of energy labelling and/or MEPS:

The Minimum Energy Performance Standards requirements are set out as minimum EER levels. These are set out in the table below.

MEPS: MINIMUM EER FOR AIR COOLED CONDENSER AIRCONDITIONERS (from AS/NZS 3823.2-2009)

Product Description

MEPS
2006-07

MEPS
2010*

MEPS
2011*

Unitary - all types, <10kW, all phases

2.75

2.84

2.84

Unitary – all types, 10kW to <19kW, all phases

2.75

2.75

2.75

Split systems – all types, <4kW, all phases

3.05

3.33

3.33

Split systems – all types, 4kW to <10kW, all phases

2.75

2.93

2.93

Split systems – all types, 10kW to <19kW, all phases

2.75

2.75

2.75

Ducted systems – all types, <19kW, single phase

2.50

2.75

2.75

Ducted systems – all types, <10kW, three phase

2.50

2.75

2.75

Ducted systems – all types, 10kW to <19kW, three phase

2.75

2.75

2.75

All configurations, all types, 19kW to 39kW, all phases

3.05

3.05

3.05

All configurations, all types, <39kW to 65kW, all phases

2.75

2.75

2.75

*The EER levels 2010 will be based on operating EER, while the levels in 2011 will be based on annual EER.
Note: Unitary are mostly window wall units or packaged systems. Types refer to cooling only or reverse cycle. Air source only – separate MEPS levels are specifi ed for water source heat pumps – refer to AS/NZS3823.2-2009 for details
equipmentsafety@dir.qld.gov.au

MEPS—MINIMUM REQUIREMENTS FOR WATER SOURCE HEAT PUMPS AND
AIR CONDITIONERS AT RATED CAPACITY
(see Note)

Cooling and/or Heating Capacity

Minimum EER and/or COP
1 Apr 2010

Minimum AEER and/or ACOP
1 Apr 2011

<39.0 kW 3.50 3.50
<39.0 kW 3.20 3.20
NOTE: This table includes requirements for air conditioners with water cooled condensers and water sourced heat pumps.

The rated capacity is defined under condition T1 in AS/NZS 3823.1.1 or AS/NZS3823.1.2 or AS/NZS3823.1.3, as applicable.

For MEPS purposes:

Note that where a product is registered for energy labelling as well as MEPS, only physical tests are permitted (ie simulation is not allowed). For products registered for energy labelling, a test report must also be submitted to show that the model is capable of meeting the maximum cooling test requirement.

Note that heating only units (with no cooling function) are not required to be registered for MEPS.

A copy of the standard can be purchased from SAI Global under licence from Standards Australia.

Find out how to make an application for energy labelling and/or MEPS.

 

This page last modified 22 April 2010

Comments to Contact | Copyright & disclaimer | Privacy | Accessibility
© Commonwealth of Australia
Website credits


Australian Greenhouse Office Logo   Valid XHTML 1.0 Transitional Valid CSS!